|
Analyzer/Transmitter Operational Data |
| Ambient
condition requirements |
Temperature –
minus 40 degrees C to 55 degrees C
Humidity – 0 to 100 percent
Altitude – 0 to 10,000 feet |
| Display |
The display
is a two-line, backlit LCD with extended temperature range and
resistant to UV. |
| Sensor Check |
Automatic
self diagnostics |
| Sensor to
Analyzer Distance |
610 meters |
| Power
Requirements |
230 VAC 50 Hz |
| Accuracy |
1% of reading
or 0.02 ppm, whichever is greater |
| Sensitivity
or Resolution |
0.01 ppm |
| Stability
(per 24 hr period) |
0.01 ppm |
| Repeatability |
0.01 ppm |
| Temperature
Drift |
Not
applicable |
| Zero Output
Reading |
Not
applicable |
| Consequence
of Loss of Sample or Power |
User
selectable |
| Measuring
ranges |
0.0 to 25.0 ppm
0 to 50 degrees C |
| Temperature
compensation |
0 to 50
degrees C |
| Calibration
Method |
Not required
nor recommend during initial startup. Provisions for one-point in
water calibration provided. |
| Memory backup |
Yes |
|
Analyzer/Transmitter Outputs |
| Analog |
0 to 20 or 4
to 20 milliamp (user selectable) for DO
0 to 20 or 4 to 20 milliamp (user selectable) for Temperature |
| Digital
communication |
Modbus RTU
RS-232 |
| Relay
|
There are
three independently programmable set point control relays and one jet
clean relay. Relay 1 & 2 are Form-C with contacts rated 10/6 amps
resistive load at 125/250 VAC and relay 3 & 4 are Form-A with contacts
rated 10/6 amps resistive load at 125/250 VAC. |
|
Analyzer/Transmitter Mechanical Data |
| Enclosure
Rating |
NEMA 4X |
| Mounting
Configurations |
Horizontal
handrail
Vertical handrail
Wall mount |
| Net Weight |
Shipping
weight is approximately 4kg |
|
DO Sensor Data |
| Electrode
Materials |
No electrode |
| Electrolyte
Materials |
No
electrolyte |
| Sensor Drift |
Less than 1%
per year |
| Wetted
Materials |
Epoxy,
silicon, and polyurethane |
| Temperature
Range |
0 to 50
degrees C |
| Minimum Flow
Rate |
No flow
required |
| Maximum
Pressure |
100 psi |
| Measuring
Range |
0.00 to 25.0
ppm |
| Response Time |
90% in less
than 60 seconds |
| Membrane
Thickness |
No membrane |
| Principle of
Operation |
The sensor is
an optical type sensor that measures the fluorescence and quenching
reactions of a ruthenium complex that is immobilized in a sol-gel
matrix. |
| Sensor Cable |
4 conductor,
22 AWG, polyurethane jacket |
| Temperature
Sensor |
thermistor |
| Cleaning
System |
Not required
in most applications. Air or water wash option available. |
|
Sensor/Analyzer Data |
| Documentation
Provided |
Operator
Manual, Packing list, Mod bus RTU appendix |
| Installation
and Start-Up Requirements |
INSTALLATION and
STARTUP
A rear rail mounting kit is available to mount the standard
enclosure to 2" handrail (see Drawing IIG01N010).
Mount the sensor in the desired location (see drawing IIG02N005
& IIG02N004).
Open the enclosure of the Dissolved Oxygen Analyzer. Pass all
connection cables through conduit or glands in the bottom of the
enclosure (conduit and glands not supplied). The sensor input
connections are made to the terminal block labeled TB5 (see drawing
IIG01R011). The four wires are color coded and there is a cable
shield. Connect the RED wire to the terminal labeled "RED". Connect
the GREEN wire to the terminal labeled "GRN". Connect the WHITE wire
to the terminal labeled "WHT". Connect the BLACK wire to the
terminal labeled "BLK". Connect the cable SHIELD to the terminal
labeled "SHLD". Power connections are made to the terminal block
labeled TB3. The analog outputs are available on the terminal block
labeled TB1 and the relay outputs are available on the terminal
block labeled TB6.
Check switch S4 on the circuit board to be sure that it is set
for the type of power being used (115 volts or 230 volts). Turn
power "on" by using switch S3. Close and secure the enclosure.
After being turned on, the unit will initialize and then jump
into the "RUN" mode and begin displaying the Dissolved Oxygen
content and the temperature.
Note: The Model 10 sensor undergoes a thorough and
accurate test and calibration procedure before shipment from the
factory. Calibration of the system at startup is not necessary and is
not recommended.
The first time the unit is powered up with the sensor in the
process, 15 minutes are required for the sensor to stabilize. The
reading will drift slightly during this period. After approximately 15
minutes the sensor will respond correctly. In the event the sensor is
removed from the process for a short period of time, the sensor should
be allowed to stabilize for approximately 10 minutes after it is put
back in the process. |
| Recommended
Spare Parts |
none |
| Maintenance
Requirements |
MAINTENANCE The analyzer does not require any periodic
maintenance. The sensor must be kept free of debris for accurate
readings.
Model 10 D.O. Sensor: In normal wastewater aeration basins the
Model 10 Sensor will not require a jet clean system; however it is
important that the aqueous sample to be measured be allowed to come in
contact with the measuring surface. The sensor should be visually
inspected on a monthly basis to insure that rags and hair have not
completely covered the measuring surface. During this time we
recommend rinsing the sensor with a water hose.
In systems with high bio-slim and scaling, the integrated jet clean
system is recommended to be used to prevent the slim and scale from
attaching itself to the measuring surface.
Fouling conditions at wastewater treatment facilities varies
considerably from plant to plant. Experience gained during the first
few months of sensor operation will allow the plant operators to
determine their own reasonable schedule of sensor inspection. In no
case should this inspection interval exceed one year. |
| Sensor
Storage Requirements When Out of Service |
none |
| Level of
Skill (required to operate, maintain and calibrate instrument) |
Minimal
|
| Special Tools
or Other Devices Required for Maintenance and Calibration |
none |
| Warranty
|
2 year |
| |
Top |